Mã sản phẩm: PE8324
Mô tả: eco PDU
Xuất xứ: Taiwan
Bảo hành: 12 tháng
As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE8324 eco PDUs are intelligent PDUs that contain 24 AC outlets and are available in various IEC socket configurations. Models in the advanced PE8 ranges feature NRGence´s proactive overload protection, which automatically powers off the last outlet that caused the current overload.
Function | PE8324A | PE8324B | PE8324G |
Electrical | |||
Nominal Input Voltage | 100 – 120 VAC | 100 – 240 VAC | 100 – 240 VAC |
Maximum Input Current | 30A(Max); 24A(UL de-rated) | 30A Max; 24A (UL de-rated) | 32A Max |
Input Frequency | 50-60 Hz | 50-60 Hz | 50-60 Hz |
Input Connection | NEMA L5-30P | NEMA L6-30P | IEC 60309 32A |
Input Power | 6240 VA(Max); 4992 VA(UL de-rated) | 6240 VA(Max); 4992 VA(UL de-rated) | 7360 VA(Max) |
Outlet Type | Total: 24 x NEMA 5-15R Bank1-1: Outlet 1 – 8; 8 x NEMA 5-15R Bank1-2: Outlet 9 – 16; 8 x NEMA 5-15R Bank2: Outlet 17 – 24; 8 x NEMA 5-15R |
Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19 |
Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19 |
Nominal Output Voltage | 100 – 120 VAC | 100 – 240 VAC | 100 – 240 VAC |
Maximum Output Current (Outlet) | NEMA 5-15R: 15A(Max); 12A(UL de-rated) | C13: 15A(Max); 12A(UL de-rated) C19: 15A(Max); 12A(UL de-rated) |
C13: 10A(Max) C19: 16A(Max); TUV De-rated 15A(Max) |
Maximum Output Current (Bank) | 15A(Max); 12A(UL de-rated) | 15A(Max); 12A(UL de-rated) | 16A(Max); TUV De-rated 15A(Max) |
Maximum Output Current (Total) | 30A(Max); 24A(UL de-rated) | 30A(Max); 24A(UL de-rated) | 32A(Max); TUV De-rated 30A(Max) |
Breakers | 2 x 16A UL489 Breaker | 2 x 16A UL489 Breaker | 2 x 16A UL489 Breaker |
Metering | Outlet Level Current, Voltage, VA, PF, KWh Monitoring | Outlet Level Current, Voltage, VA, PF, KWh Monitoring | Outlet Level Current, Voltage, VA, PF, KWh Monitoring |
Outlet Switching | Yes | Yes | Yes |
Environment Sensor Ports | 4 | 4 | 4 |
Metering Accuracy | Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Voltage Range: 100VAC ~ 250VAC +/-1% Power Range: 100W ~ Maximum Capacity +/- 2% Current Range: 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties | |||
Dimensions (L x W x H) | 177.50 x 6.60 x 4.40 cm (69.88 x 2.6 x 1.73 in.) |
177.50 x 6.60 x 4.40 cm (69.88 x 2.6 x 1.73 in.) |
177.50 x 6.60 x 4.40 cm (69.88 x 2.6 x 1.73 in.) |
Weight | 6.33 kg ( 13.94 lb ) | 6.33 kg ( 13.94 lb ) | 6.33 kg ( 13.94 lb ) |
Power Cord Length | 1.6 m | 1.6 m | 1.6 m |
Environmental | |||
Temperature (Operating / Storage) | 0 – 50°C / -20 – 60°C | 0 – 50°C / -20 – 60°C | 0 – 40°C / -20 – 60°C |
Humidity (Operating & Storage) | 0 – 80% RH, Non-Condensing | 0 – 80% RH, Non-Condensing | 0 – 80% RH, Non-Condensing |
Compliance | |||
EMC Verification | FCC Part 15 Class A, Others by Request | FCC Part 15 Class A, Others by Request | CE, Others by Request |
Safety Verification | By Request | By Request | CE-LVD, Others by Request |